RS control station

Flow temperature control for surface heating circuits

RS control stations

  • for flow temperature control, preferably of panel heating systems with max. 14KW heat requirement
  • Combination underfloor heating with or without storey heating for connection to flow pipes with high temperature level for 2 ... 10 underfloor heating circuits and 0 ... 2 radiator circuits (further heating circuits on request)
  • pre-installed and leak-tested ready for connection
  • on sound-absorbing brackets (DIN 4109)
  • hydraulically decoupled
  • Overheating protection wired at the factory (optional)
  • optionally with weather-compensated control TRHK114
Components:
  • Wilo PARA 25-130/6-43 SC pump - Flow temperature control by means of adjustable thermostatic valve (kvs value 2.3)
  • Backflow preventer and flow thermometer
  • Fixed value control TKK-TF (thermostatic head, control range 20-70°C and flow temperature sensor ½")
Connections:
  • primary side: ¾" internal thread
  • secondary side: ¾" AG Eurocone for standard compression fittings

Heating circuit manifold

Floor manifold 1"
  • Flow pipe:
    • integrated flow meter (0-5 l/min) with sight glass and flow indicator
    • easy to regulate, shut off and seal
    • End piece with air vent and SFE tap
  • Return flow:
    • integrated thermostatic valves kvs value 1.2 m³/h
    • M30 x 1.5 mm AG for commercially available actuators (stroke 5 mm)
Storey manifold 1"
  • Flow and return: Venting

Connection assembly (primary side)

without heat meter section
  • Flow and return: ¾" ball valves and detachable screw connections

alternatively

with universal heat meter section - type UNI
  • Flow pipe:
    • ¾" ball valve with direct sensor connection M10x1 for direct sensor DF ∅5.2
  • Return flow:
    • Long nipple ¾"x110 mm for mounting heat meters (observe installation dimensions)
    • before and after detachable screw connections and ¾" ball valves, ball valve on primary side with direct sensor connection

Installation in a built-in cabinet

  • Design suitable for installation in masonry, stud walls and pre-wall installation, among others
  • Cabinet installation depth: 110...160 mm adjustable
  • galvanised flush-mounted box (110 mm deep)
  • break-out bushings as required
  • height-adjustable feet up to 65 mm and depth-adjustable removable screed baffle / baffle plate
  • Enclosure height 730...795 mm - usable installation height 610 mm
  • Cover:
    • depth-adjustable powder-coated (similar to white RAL9016) frame and plug-in door with slot lock
    • other cover variants on request

alternatively

Installation in surface-mounted cabinet

  • Cabinet depth: 140 mm
  • made of galvanised sheet steel
  • free feed-throughs at the bottom
  • removable cover / screed baffle / baffle plate
  • height-adjustable feet - enclosure height 700...750 mm
  • usable installation height 620 mm
  • Cover:
    • powder-coated (similar to white RAL9016)
    • Plug-in door with slot lock

Downloads

Similar products

Customised solutions

In most cases, our successful and diverse product portfolio offers a solution for your building technology needs. Nevertheless, it may be the case that only a customised building technology solution can help with your individual requirements. We are also your specialised partner in this case and are sure to find a solution for your individual application.